AIR HANDLING

AHU 70mm Frame

AHU 70mm Frame

AIR HANDLING UNIT

The Air Design bespoke 70mm frame range with 50mm panels covers an airflow duty envelope from 0.81 to 13.5m³/s.

Designed to offer complete flexibility with low height options and width combinations, with the added benefit of using industry standard filter sizes.

Contact Us Product Enquiry

Share

Airflow Rates (m3/s)

Frame Panel 0.10 0.25 0.33 0.50 0.75 0.88 1.00 1.25 1.50 2.00 2.50 2.70 3.00 4.00 5.50 6.50 8.00 9.00 9.25 9.50 9.75 13.5
70mm 50mm

Filter Selection Table

Unit Ref Unit Width Unit Height Filter Width Filter Height Velocity 1.50 2.00 2.50
AD71260 1290 790 1200 600 Filter 1.08 1.44 1.80
Heater 0.86 1.14 1.43
Cooler 0.81 1.08 1.35
AD71560 1585 790 1500 600 Filter 1.35 1.80 2.25
Heater 1.11 1.48 1.85
Cooler 1.05 1.40 1.75
AD712100 1290 1190 1200 1000 Filter 1.80 2.40 3.00
Heater 1.48 1.97 2.46
Cooler 1.43 1.91 2.38
AD712120 1290 1390 1200 1200 Filter 2.16 2.88 3.60
Heater 1.76 2.35 2.94
Cooler 1.72 2.29 2.86
AD715120 1585 1390 1500 1500 Filter 2.70 3.60 4.50
Heater 2.28 3.04 3.80
Cooler 2.22 2.96 3.70
AD715150 1585 1690 1500 1500 Filter 3.38 4.50 5.63
Heater 2.84 3.78 4.73
Cooler 2.77 3.70 4.62
AD721120 2180 1390 2100 1200 Filter 3.78 5.04 6.30
Heater 3.31 4.41 5.51
Cooler 3.22 4.29 5.36
AD720150 2080 1690 2000 1500 Filter 4.50 6.00 7.50
Heater 3.89 5.19 6.49
Cooler 3.81 5.08 6.35
AD724150 2480 1690 2400 1500 Filter 5.40 7.20 9.00
Heater 4.73 6.31 7.89
Cooler 4.63 6.17 7.71
AD724180 2480 1990 2400 1800 Filter 6.48 8.64 10.80
Heater 5.76 7.68 9.60
Cooler 5.66 7.54 9.43
AD730180 3075 1990 3000 1800 Filter 8.10 10.80 13.50
Heater 7.08 9.44 11.80
Cooler 6.96 9.27 11.59

Dimensions in mm. Velocity in m/s. Data for design guidance only. We reserve the right to alter product specification without prior notice.